EasyManuals Logo
Home>ABB>Controller>REC650 ANSI

ABB REC650 ANSI User Manual

ABB REC650 ANSI
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #208 background imageLoading...
Page #208 background image
8.3.6.3 Design
ANSI08000009_en_1.vsd
RESTORE
PICKUP
PICKUP
TRIP
Pickup
&
Trip
Output
Logic
BLOCK
Frequency
100 ms
Comparator
If
[PUFreqGrad<0
AND
df/dt < PUFreqGrad]
OR
[PUFreqGrad>0
AND
df/dt > PUFreqGrad]
Then
PICKUP
Comparator
f > RestoreFreq
OR
Definite Time Delay
tTrip
tRestore
BLKDMAGN
Rate-of-Change
of Frequency
BLOCK
freqNotValid
ANSI08000009 V1 EN
Figure 85: Schematic design of Rate-of-change frequency protection SAPFRC (81)
8.3.7 Technical data
Table 148: SAPFRC (81) technical data
Function
Range or value Accuracy
Operate value, pickup function (-10.00-10.00) Hz/s ± 10.0 mHz/s
Operate value, restore enable
frequency
(45.00 - 65.00) Hz ± 2.0 mHz
Timers (0.000 - 60.000) s <130 ms
Operate time, pickup function At 50 Hz: 100 ms typically
At 60 Hz: 80 ms typically
-
Section 8 1MRK 511 287-UUS A
Frequency protection
202
Technical manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REC650 ANSI and is the answer not in the manual?

ABB REC650 ANSI Specifications

General IconGeneral
BrandABB
ModelREC650 ANSI
CategoryController
LanguageEnglish

Related product manuals