10.13.3 Signals
Table 251: I103GENCMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of command
Table 252: I103GENCMD Output signals
Name Type Description
CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON
10.13.4 Settings
Table 253: I103GENCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 1 - 255 - 1 1 Information number for command output
(1-255)
10.14 IED commands with position and select for IEC
60870-5-103 I103POSCMD
10.14.1 Functionality
I103POSCMD has double-point position indicators that are getting the position value as
an integer (for example from the POSITION output of the SCSWI function block) and
sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not define
the use of values 0 and 3 . However, when connected to a switching device, these values
are transmitted.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate type of
control)
1MRK 511 287-UUS A Section 10
Control
363
Technical manual