14.7.5 Settings
Table 476: GOOSEMVRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable/Disable
14.7.6 Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the float values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
14.8 GOOSE function block to receive a single point value
GOOSESPRCV
14.8.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
single point value
GOOSESPRCV - -
Section 14 1MRK 511 287-UUS A
Station communication
574
Technical manual