Table 360: VMSQI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
3V0ZeroDb 0 - 100000 m% 1 500 Zero point clamping
3V0HiHiLim 0 - 2000000 V 1 288000 High High limit (physical value)
3V0HiLim 0 - 2000000 V 1 258000 High limit (physical value)
3V0LowLim 0 - 2000000 V 1 213000 Low limit (physical value)
3V0LowLowLim 0 - 2000000 V 1 198000 Low Low limit (physical value)
V1ZeroDb 0 - 100000 m% 1 500 Zero point clamping
V1HiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)
V1HiLim 0 - 2000000 V 1 86000 High limit (physical value)
V1LowLim 0 - 2000000 V 1 71000 Low limit (physical value)
V1LowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)
V1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is common
for all limits
V2ZeroDb 0 - 100000 m% 1 500 Zero point clamping
V2HiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)
V2HiLim 0 - 2000000 V 1 86000 High limit (physical value)
V2LowLim 0 - 2000000 V 1 71000 Low limit (physical value)
V2LowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)
12.1.6.5 Monitored data
Table 361: VMSQI Monitored data
Name
Type Values (Range) Unit Description
3V0 REAL - kV 3U0 Amplitude
3V0ANGL REAL - deg 3U0 Angle
V1 REAL - kV U1 Amplitude
V1ANGL REAL - deg U1 Angle
V2 REAL - kV U2 Amplitude
V2ANGL REAL - deg U2 Angle
Section 12 1MRK 511 287-UUS A
Monitoring
436
Technical manual

Table of Contents