Name Type Description
B1SEL BOOLEAN Bus1 selected
B2SEL BOOLEAN Bus2 selected
L1SEL BOOLEAN Line1 selected
L2SEL BOOLEAN Line2 selected
SYNPROGR BOOLEAN Synchronizing in progress
SYNFAIL BOOLEAN Synchronizing failed
FRDIFSYN BOOLEAN Frequency difference out of limit for synchronizing
FRDERIVA BOOLEAN Frequency derivative out of limit for synchronizing
VOKSC BOOLEAN Voltage magnitudes above set limits
VDIFFSC BOOLEAN Voltage difference out of limit
FRDIFFA BOOLEAN Frequency difference out of limit for Auto operation
PHDIFFA BOOLEAN Phase angle difference out of limit for Auto operation
FRDIFFM BOOLEAN Frequency difference out of limit for Manual operation
PHDIFFM BOOLEAN Phase angle difference out of limit for Manual Operation
INADVCLS BOOLEAN Inadvertent circuit breaker closing
VDIFFME REAL Calculated difference of voltage in p.u of set voltage
base value
FRDIFFME REAL Calculated difference of frequency
PHDIFFME REAL Calculated difference of phase angle
Vbus REAL Bus voltage
VLine REAL Line voltage
MODEAEN INTEGER Selected mode for automatic energizing
MODEMEN INTEGER Selected mode for manual energizing
10.1.5 Settings
Table 167: SESRSYN (25) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
CBConfig No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
-
- No voltage sel. Select CB configuration
VRatio 0.500 - 2.000 - 0.001 1.000 Multiplication factor for minor internal
adjustmernt of measured line voltage for
synchro functions
PhaseShift
-180 - 180 Deg 1 0 Additional phase angle for selected line voltage
Table continues on next page