16.3 Outputs
16.3.1 Outputs for tripping, controlling and signalling
Output contacts PO1, PO2 and PO3 are power output contacts used, for example, for
controlling circuit breakers.
Each signal connector terminal is connected with one 14 or 16 Gauge wire. Use 12 or 14
Gauge wire for CB trip circuit.
The connected DC voltage to outputs with trip circuit supervision (TCM)
must have correct polarity or the trip circuit supervision TCSSCBR
function will not operate properly.
Table 539: Output contacts X317, 3U full 19”
Terminal Description PCM600 info
Hardware module
instance
Hardware channel
Power output 1, normally open (TCM)
X317-1 - PSM_102 BO1_PO_TCM
X317-2 +
Power output 2, normally open (TCM)
X317-3 - PSM_102 BO2_PO_TCM
X317-4 +
Power output 3, normally open (TCM)
X317-5 - PSM_102 BO3_PO_TCM
X317-6 +
X317-7 Power output 4, normally open PSM_102 BO4_PO
X317-8
X317-9 Power output 5, normally open PSM_102 BO5_PO
X317-10
X317-11 Power output 6, normally open PSM_102 BO6_PO
X317-12
1MRK 511 287-UUS A Section 16
IED physical connections
637
Technical manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REC650 ANSI and is the answer not in the manual?

ABB REC650 ANSI Specifications

General IconGeneral
BrandABB
ModelREC650 ANSI
CategoryController
LanguageEnglish

Related product manuals