12.20.4 Settings
Table 435: I103MEASUSR Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 25 Function type (1-255)
InfNo 1 - 255 - 1 1 Information number for measurands (1-255)
MaxMeasur1 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 1
MaxMeasur2 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 2
MaxMeasur3 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 3
MaxMeasur4 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 4
MaxMeasur5 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 5
MaxMeasur6 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 6
MaxMeasur7 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 7
MaxMeasur8 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 8
MaxMeasur9 0.05 -
10000000000.00
- 0.05 1000.00 Maximum value for measurement on input 9
12.21 Function status auto-recloser for IEC 60870-5-103
I103AR
12.21.1 Functionality
I103AR is a function block with defined functions for autorecloser indications in monitor
direction. This block includes the FunctionType parameter, and the information number
parameter is defined for each output signal.
Section 12 1MRK 511 287-UUS A
Monitoring
542
Technical manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REC650 ANSI and is the answer not in the manual?

ABB REC650 ANSI Specifications

General IconGeneral
BrandABB
ModelREC650 ANSI
CategoryController
LanguageEnglish

Related product manuals