12.23.2 Function block
I103FLTPROT
BLOCK
64_PU_A
65_PU_B
66_PU_C
67_STIN
68_TRGEN
69_TR_A
70_TR_B
71_TR_C
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTR_A
87_MTR_B
88_MTR_C
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
ANSI10000291-1-en.vsd
ANSI10000291 V1 EN
Figure 246: I103FLTPROT function block
12.23.3 Signals
Table 440: I103FLTPROT Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of status reporting.
64_PU_A BOOLEAN 0 Information number 64, start phase A
65_PU_B BOOLEAN 0 Information number 65, start phase B
66_PU_C BOOLEAN 0 Information number 66, start phase C
67_STIN BOOLEAN 0 Information number 67, start residual current IN
68_TRGEN BOOLEAN 0 Information number 68, trip general
69_TR_A BOOLEAN 0 Information number 69, trip phase A
70_TR_B BOOLEAN 0 Information number 70, trip phase B
71_TR_C BOOLEAN 0 Information number 71, trip phase C
72_TRBKUP BOOLEAN 0 Information number 72, back up trip I>>
Table continues on next page
1MRK 511 287-UUS A Section 12
Monitoring
545
Technical manual