5.4.3 Front communication
The RJ-45 port in the LHMI enables front communication.
• The green uplink LED on the left is lit when the cable is successfully connected
to the port.
• The yellow LED is not used; it is always off.
IEC13000280-1-en.vsd
1
2
GUID-AACFC753-BFB9-47FE-9512-3C4180731A1B V1 EN
Figure 37: RJ-45 communication port and green indicator LED
1 RJ-45 connector
2 Green indicator LED
The default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.254.0. It can be set through the local HMI path Main
menu/Configuration/Communication/Ethernet configuration/FRONT port/
AP_FRONT.
Do not connect the IED front port to a LAN. Connect only a single
local PC with PCM600 to the front port. It is only intended for
temporary use, such as commissioning and testing.
1MRK 502 071-UEN - Section 5
Local HMI
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 101
Application manual