Operation: This is used to disable/enable the operation of gas medium supervision i.e.
Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuit
breaker.
PresLOLimit: This is used to set the limit for a pressure lockout condition in the circuit
breaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in the
circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in the
circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication, given
in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout indication,
given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set time
delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set time
delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a set
time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.
17.3 Liquid medium supervision SSIML
17.3.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function SSIML - 71
Section 17 1MRK 502 071-UEN -
Monitoring
636 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual