G
SA PTUF
81U f<
SA PTUF
81 f<
SA PTOF
81O f>
SA PTOF
81 f>
UV2 PTUV
27 2(3U<)
OV2 PTOV
59 2(3U>)
VN MMXU
MET UN
V MSQI
MET Usqi
CC RBRF
50BF 3I>BF
GOP PDOP
32 P>
GUP PDUP
37 P<
GS PTTR
49 S θ>
C MMXU
MET I
GEN PDIF
87G 3Id/I>
ZGV PDIS
21 Z<
CV GAPC
64R Re<
CV GAPC
2(i>/U<)
LEX PDIS
40 Φ <
DRP RDRE
DFR/SER DR
OEX PVPH
24 U/f>
ETP MMTR
MET W/Varh
CV MMXN
MET P/Q
+
RXTTE4
REG670 A20 – Generator differential + backup protection 12AI (7I + 5U)
Y
Y
ROV2 PTOV
59N 2(U0>)
AEG PVOC
50AE U/I>
SMP PTRC
94 1→0
ROV2 PTOV
59N 2(U0>)
V MMXU
MET U
GEN_QA1
GEN_TRM_VT
GEN_TRM_CT
ROT_INJ_VT
ROT_INJ_CT
GEN_SP_CT
GEN_SP_VT
OC4 PTOC
51_67 4(3I>)
C MSQI
MET Isqi
C MMXU
MET I
SES RSYN
25 SC/VC
CCS SPVC
87 INd/I
ROTI PHIZ
64R R<
OOS PPAM
78 Ucos
HZ PDIF
87 Id>
SDE PSDE
67N IN>
T2W PDIF
87T 3Id/I>
STEF PHIZ
59THD U3d/N
EF4 PTOC
51N_67N
4(IN>)
SA PFRC
81 df/dt<>
Other Functions available from the function library
Optional Functions
NS4 PTOC
46I2 4(I2>)
PSP PPAM
78 Ucos
CC PDSC
52PD PD
PH PIOC
50 3I>>
EF PIOC
50N IN>>
VDC PTOV
60 Ud>
Q CBAY
3 Control
GR PTTR
49R θ>
TCM YLTC
84 ↑↓
VD SPVC
60 Ud>
FTA QFVR
81A f<>
VR PVOC
51V
2(I>/U<)
Q CRSV
3 Control
S CILO
3 Control
S CSWI
3 Control
S SCBR
Control
ZMH PDIS
21 Z<
TR PTTR
49 θ>
ZDM RDIR
21D Z<_>
IEC11000068-6-en.vsdx
S SIML
71
S SIMG
63
S SCBR
Control
S SCBR
Control
S XCBR
3 Control
PMU REP
STTI PHIZ
64S R<
S XSWI
3 Control
FUF SPVC
U>/I<
NS2 PTOC
46 I2>
IEC11000068 V6 EN
Figure 8: Typical generator protection application with generator differential
and back-up protection, including 12 analog inputs transformers in
half 19" case size.
3.1.1.2 Description of configuration B30
REG670 B30 configuration is used in applications where generator protection and
backup protection for surrounding primary equipment within one IED is required.
REG670 B30 is always delivered in 1/1 of 19" case size. Thus 24 analogue inputs are
available. This configuration includes generator low impedance, differential
protection and all other typically required generator protection functions. In figure
9,
this configuration is shown.
Section 3 1MRK 502 071-UEN -
Configuration
58 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Other manuals for ABB REG670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REG670 and is the answer not in the manual?

ABB REG670 Specifications

General IconGeneral
BrandABB
ModelREG670
CategoryProtection Device
LanguageEnglish

Related product manuals