EasyManuals Logo

ABB REG670 Applications Manual

ABB REG670
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #317 background imageLoading...
Page #317 background image
The settings of all the zones is provided in terms of percentage of impedance based on
current and voltage ratings of the generator.
8.9.2.2 Zone 1 operation
Zone 1 is used as fast selective tripping for phase-to-phase faults and three–phase
faults in the generator, on the terminal leads and LV side of generator transformer.
Since generator is high impedance earthed, the fault current for phase-to-earth faults
will be too low and impedance protection is not intended to operate for these faults.
The measuring loops used for zone1 are given below.
Zone 1 measuring loops for phase-to-phase faults and three–phase faults on the
primary side of the generator transformer are:
Sl.No Phase-to-phase loop Voltage phasor Current phasor
1 L1–L2 UL1L2 IL1L2
2 L2–L3 UL2L3 IL2L3
2 L3–L1 UL3L1 IL3L1
UL1L2, UL2L3, UL3L1 are three phase-to-phase voltages. IL1L2,
IL2L3, IL3L1 are the three phase-to-phase currents.
For this application the zone 1 element is typically set to see 75% of the transformer
impedance.
8.9.2.3 Zone 2 operation
Zone 2 can be used to cover up to the HV side of the transformer and the HV bus bar,
and is usually set to cover 125% of the generator transformer impedance. The time to
trip must be provided in order to coordinate with the zone 1 element on the shortest
outgoing line from the bus.
Zone2 will provide protection for phase-to-earth, phase-to-phase and three-phase
faults on the HV side of the system. All these faults can be detected using three phase-
to-phase loops or Enhanced reach loop (The phase-to-earth loop with maximum phase
current).
Two options are provided for measuring loops used for zone 2, which is set by the user.
The measuring loops used for zone 2 with different options are:
Phase-to-phase loops
Phase-to-phase loop
Voltage phasor Current phasor
L1–L2 UL1L2 IL1L2
L2–L3 UL2L3 IL2L3
L3–L1 UL3L1 IL3L1
1MRK 502 071-UEN - Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 311
Application manual

Table of Contents

Other manuals for ABB REG670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REG670 and is the answer not in the manual?

ABB REG670 Specifications

General IconGeneral
BrandABB
ModelREG670
CategoryProtection Device
LanguageEnglish

Related product manuals