16.13 Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
16.13.1 Identification
Function Description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator TEIGAPC - -
16.13.2 Application
The function TEIGAPC is used for user-defined logics and it can also be used for
different purposes internally in the IED. An application example is the integration of
elapsed time during the measurement of neutral point voltage or neutral current at
earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 999999.9 seconds.
16.13.3 Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit float
representation
99 999.99 seconds < tAlarm ≤ 999 999.0 seconds
99 999.99 seconds < tWarning ≤ 999 999.0 seconds
Note that tAlarm and tWarning are independent settings, that is, there
is no check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 999999.9 seconds.
1MRK 502 071-UEN - Section 16
Logic
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 617
Application manual

Table of Contents

Other manuals for ABB REG670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REG670 and is the answer not in the manual?

ABB REG670 Specifications

General IconGeneral
BrandABB
ModelREG670
CategoryProtection Device
LanguageEnglish

Related product manuals