Troubleshooting ESIE11-02
3–32 Part 3 – Troubleshooting
3
1
3
4
5
4.7 Parameter and Parameter Level Overview
Overview The table below shows the full list of all parameters with the corresponding setpoint according to the
unit type. This table can be used as reference when during programming of the controller a parameter
was changed which was not indicated in the ‘replacing the controller’ procedure.
(*) Bold = different from default, “-” = not applicable because of other setting
(**) level type (L-P): D=Direct, U=User, S=Super user, F=Factory
Parameter code
Description
SW version
Default level type (L-P)
Modified level type (L-P)
Carel default value (S-P)
Unit of measurement
EUWA*5-8-10-12K* standard
EUWA*5-8-10-12K* OP ZL
EUWA*5-8-10-12K* OP ZH
EUWA*16-20-24K* standard
EUWA*16-20-24K* OP ZL
EUWA*16-20-24K* OP ZH
EUWY*5-8-10-12K* standard
EUWY*5-8-10-12K* OP ZL
EUWY*5-8-10-12K* OP ZH
EUWY*16-20-24K* standard
EUWY*16-20-24K* OP ZL
EUWY*16-20-24K* OP ZH
R/W
Supervis variable
Modbus
Type
1. Probe setting
parameters (/*)
---
/01Probe type B1 1,9FF1 - 111111111111R/W11DIG
/02 Probe type B2 1,9 F F 0 - 111111111111R/W 2 2 DIG
/03 Probe type B3 1,9 F F 0 - 111111111111R/W 14 221 INT
/04Probe type B4 1,9FF0 - 000000000000R/W15222INT
/13Probe B1 calibration 1,9FF0°C/°F000000000000R/W33ANA
/14Probe B2 calibration 1,9FF0°C/°F000000000000R/W44ANA
/15Probe B3 calibration 1,9FF0°C/°F000000000000R/W55ANA
/16 1,9FF0°C/°F----------------
/21Digital filter 1,9UF4 - 444444444444R/W20227INT
/22Input limitation 1,9UF8 - 888888888888R/W21228INT
/23Measurement unit 1,9UU0 - 000000000000R/W55DIG
2. Anti-freeze/supporting
heater setting parameters
(A*)
---
A01 Anti-freeze alarm setpoint 1,9 U F C4-12-6,54-12-6,54-12-6,54-12-6,5R/W 11 11 ANA
A02 Anti-freeze alarm
hysteresis
1,9 U F C3,5 3,5 3,5 3,5 3,5 3,5 3,5 3,5 3,5 3,5 3,5 3,5 R/W 12 12 ANA
A03 Bypass time for anti-freeze
alarm
1,9 U F 0sec000000000000R/W22229ANA
A04 Anti-freeze heater setpoint 1,9 U F C410-5410-5410-5410-5R/W 13 13 ANA
A05 Anti-freeze heater
hysteresis
1,9 U F C333333333333R/W 14 14 ANA
A06Supporting heaters probe1,9FF0 - 000000000000R/W66DIG
A07 Limit anti-freeze alarm set 1,9 F F -40 °C -15 -15 -15 -15 -15 -15 -15 -15 -15 -15 -15 -15 R/W 15 15 ANA
A08 Setpoint for the supporting
heater
1,9 U F 25°C------252525252525R/W1616ANA
A09 heating support-resistance
diff.
1,9 U F 3°C------333333R/W1717ANA
A10 Automatic switch on for
antifreezing
1,9 U F 0°C------000000R/W23230INT
A11 1,9 U F - - ----------------
A12 1,9 U F - - ----------------
A13 1,9 U F - - ----------------
A14 1,9 U F - - ----------------
3. Probe reading
parameters (b*)
---
b00 Configuration of probe to
be shown on the display
1,9 U F 0 - 000000000000R/W24231INT
b01 Value read by probe B1 1,9 D D R 102 102 ANA
b02 Value read by probe B2 1,9 D D R 103 103 ANA
b03 Value read by probe B3 1,9 D D R 104 104 ANA