ESIE11-02 Functional Description
Part 2 – Functional Description 2–9
3
2
4
5
1
1.6 Compressor Timers
Compressor timers The table below shows the timers of the compressor.
Timer Interval (s) Use
Guard timer 60 The timer starts counting down when the scroll compressor
is switched OFF.
During the countdown the compressor can not be restarted.
Anti-recycling
timer
240 The timer starts counting down when the scroll compressor
is switched ON.
During the countdown the compressor can not be restarted.