ESIE11-02 General Outline
Part 1 – System Outline 1–31
3
1
4
5
1.11 Electrical Specifications: EUWA*5-8KBZW1
Electrical
specifications
The table below contains the electrical specifications
(1)
.
Model EUWAN5KBZW1 EUWAP5KBZW1 EUWAB5KBZW1 EUWAN8KBZW1 EUWAP8KBZW1 EUWAB8KBZW1
Power supply
Phase 3N~
Frequency 50 Hz
Voltage 400 V
Voltage tolerance ± 10 %
Unit
Starting current 62.2 A 63.5 A 97.9 A 99.2 A
Nominal running
current
7.7 A 9.0 A 13.6 A 14.9 A
Max. running
current
11.2 A 12.5 A 16.9 A 18.2 A
Recommended
fuses
3 x 20 gL/gG 3 x 20 gL/gG 3 x 25 gL/gG 3 x 25 gL/gG
Fans
Phase 1~
Voltage 230 V
Max. running
current
2.2 A 2.9 A
Compressor
Phase 3~
Voltage 400 V
Starting current 60.0 A 95 A
Nom. running
current
5.5 A 10.7 A
Max. running
current
9.0 A 14 A
Starting method Direct on line
Control circuit
Phase 1~
Voltage 230 V
Recommended
fuses
Factory installed
Pump
Phase__3~__3~
Voltage __ 400.0 V __ 400.0 V
Max. running
current
__ 1.3 A __ 1.3 A