ESIE11-02 General Outline
Part 1 – System Outline 1–41
3
1
4
5
1.16 Electrical Specifications: EUWY*10-12KBZW1
Electrical
specifications
The table below contains the electrical specifications
(1)
.
Model EUWYN10KBZW1 EUWYP10KBZW1 EUWYB10KBZW1 EUWYN12KBZW1 EUWYP12KBZW1 EUWYB12KBZW1
Power supply
Phase 3N~
Frequency 50 Hz
Voltage 400 V
Voltage tolerance ± 10 %
Unit
Starting current 113 A 114 A 139 A 140 A
Nominal running
current cooling
15.9 A 17.2 A 20.5 A 21.8 A
Max. running
current
19.9 A 21.2 A 26.9 A 28.2 A
Recommended
fuses
3 x 25 gL/gG 3 x 32 gL/gG 3 x 32 gL/gG 3 x 40 gL/gG
Fans
Phase 1~
Voltage 230 V
Max. running
current
2.9 A
Compressor
Phase 3~
Voltage 400 V
Starting current 110.0 A 136.0 A
Nom. running
current cooling
13.0 A 17.6 A
Max. running
current
17.0 A 24.0 A
Starting method Direct on line
Control circuit
Phase 1~
Voltage 230 V
Recommended
fuses
Factory installed
Pump
Phase __ 3~ __ 3~
Voltage __ 400.0 V __ 400.0 V
Max. running
current
__ 1.3 A __ 1.3 A