ESIE11-02 General Outline
Part 1 – System Outline 1–37
3
1
4
5
1.14 Electrical Specifications: EUWA*24KBZW1
Electrical
specifications
The table below contains the electrical specifications.
Model EUWAN24KBZW1 EUWAP24KBZW1 EUWAB24KBZW1
Power supply
Phase 3N~
Frequency 50 Hz
Voltage 400 V
Voltage tolerance ± 10 %
Unit
Starting current 139 A 142 A
Nominal running
current
41.0 A 43.7 A
Max. running
current
53.8 A 56.5 A
Recommended fuses 3 x 63 gL/gG 3 x 63 gL/gG
Fans
Phase 1~
Voltage 230 V
Max. running
current
5.8 A
Compressor
Phase 3~
Voltage 400 V
Starting current 136.0 A
Nom. running
current
17.6 A
Max. running
current
24.0 A
Starting method Direct on line
Control circuit
Phase 1~
Voltage 230/ 24 V AC (supplied by factory installed transformers)
Recommended fuses Factory installed
Crankcase heater
(E1/2 HC)
50 W 50 W
Pump
Phase __ 3~
Voltage __ 400.0 V
Max. running
current
__ 2.7 A