Chapter 9 Ethernet Specification and Operation
9-25
Category Error Code Description How to fix them
Size
H’1201012D
Consumed TAG does not
exist.
Check if the parameters in the Consumed tag are set
correctly.
H’1201012E
Produced TAG does not
exist.
Check if the parameters in the Produced tag are set
correctly.
H’12010204
Unconnected request timeout
No response from the adapter; check if the power
and the network connection for the adapter are
working properly.
H’12010302
Network bandwidth NOT
available for data
1. Check the I/O connection limit between the
scanner and the adapter.
2. Increase the RPI value or reduce the number of
connections.
H’12010315
Invalid segment in
connection path
Check the module number and the product setup file
to see if they match.
9.5.
2.2 Application Error
Category Error Code Description How to fix them
EtherNet/
IP Error
H’00010203 I/O connection timeout
1. Check the network connection status.
2. Check if the module is working properly.
3. Increase the RPI value.