6.3 Peripheral Equipment
6-7
Chap. 6 SELECTING PERIPHERAL EQUIPMENT
6.3 Peripheral Equipment
[ 1 ] Molded case circuit breaker (MCCB), ground-fault circuit interrupter
(GFCI) and magnetic contactor (MC)
[ 1.1 ] Functional overview
â–  MCCBs and GFCIs*
*With overcurrent protection
Molded Case Circuit Breakers (MCCBs) are designed to protect the power circuits between the power
supply and inverter's main circuit terminals (L1/R, L2/S and L3/T for three phase, or L1/L and L2/N for
single-phase power source) from overload or short-circuit, which in turn prevents secondary accidents
caused by the inverter malfunctioning.
Ground-Fault Circuit Interrupters (GFCIs) function in the same way as MCCBs.
Built-in overcurrent/overload protective functions protect the inverter itself from failures related to its
input/output lines.
â–  MCs
An MC can be used at both the power input and output sides of the inverter. At each side, the MC works as
described below. When inserted in the output circuit of the inverter, the MC can also switch the motor
drive power source between the inverter output and commercial power lines.
At the power source side
Insert an MC in the power source side of the inverter in order to:
(1) Forcibly cut off the inverter from the power source (generally, commercial/factory power lines) with
the protective function built into the inverter, or with the external signal input.
(2) Stop the inverter operation in an emergency when the inverter cannot interpret the stop command
due to internal/external circuit failures.
(3) Cut off the inverter from the power source when the MCCB inserted in the power source side cannot
cut it off for maintenance or inspection purpose. For the purpose only, it is recommended that you
use an MC capable of turning the MC ON/OFF manually.
When your system requires starting/stopping the motor(s) driven by the inverter with the
MC, the frequency of the starting/stopping operation should be once or less per hour. The
more frequent the operation, the shorter operation life of the MC and capacitor/s used in the
DC link bus due to thermal fatigue caused by the frequent charging of the current flow. It is
recommended that terminal commands (FWD), (REV) and (HLD) for 3-wire operation o
r
the keypad be used for starting/stopping the motor.
At the output side
Insert an MC in the power output side of the inverter in order to:
(1) Prevent externally turned-around current from being applied to the inverter power output terminals
(U, V, and W) unexpectedly. An MC should be used, for example, if a circuit that switches the motor
driving power source between the inverter output and commercial power lines is connected to the
inverter.
As application of the external current to the inverter's secondary (output) circuits may brea
k
the Insulated Gate Bipolar Transistors (IGBTs), MCs should be used in the power control
system circuits to switch the motor drive power source to the commercial power lines afte
r
the motor has come to a complete stop. Also ensure that voltage is never mistakenly applied
to the inverter output terminals due to unexpected timer operation, or similar.
(2) Drive more than one motor selectively by a single inverter.
(3) Selectively cut off the motor whose thermal overload relay or equivalent devices have been
activated.

Table of Contents

Other manuals for Fuji Electric frenic mini series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric frenic mini series and is the answer not in the manual?

Fuji Electric frenic mini series Specifications

General IconGeneral
BrandFuji Electric
Modelfrenic mini series
CategoryInverter
LanguageEnglish

Related product manuals