6-2
6.2 Selecting Wires and Crimp Terminals
This section contains information needed to select wires for connecting the inverter to commercial power
lines, motor or any of the optional/peripheral equipment. The level of electric noise issued from the
inverter or received by the inverter from external sources may vary depending upon wiring and routing. To
solve such noise-related problems, refer to Appendix A "Advantageous Use of Inverters (Notes on
electrical noise)."
Select wires that satisfy the following requirements:
- Sufficient capacity to flow the rated average current (allowable current capacity).
- Protective device coordination with an overcurrent circuit breaker such as an MCCB in the
overcurrent zone for overcurrent protection.
- Voltage loss due to the wire length is within the allowable range.
- Suitable for the type and size of terminals of the optional equipment to be used.
Recommended wires are listed below. Use these wires unless otherwise specified.
600V class of vinyl-insulated wires (IV wires)
Use this class of wire for the power circuits. This class of wire is hard to twist, so using it for the control
signal circuits is not recommended. Maximum ambient temperature for this wire is 60qC (140qF).
600V heat-resistant PVC insulated wires or 600V polyethylene insulated wires (HIV wires)
As wires in this class are smaller in diameter and more flexible than IV wires and can be used at a higher
ambient temperature 75qC (167qF), they can be used for both of the main power and control signal circuits.
To use this class of wire for the control circuits, you need to correctly twist the wires and keep the wiring
length for equipment being connected as short as possible.
600V cross-linked polyethylene-insulated wires (FSLC wires)
Use this class of wire mainly for power and grounding circuits. These wires are smaller in diameter and
more flexible than those of the IV and HIV classes of wires, meaning that these wires can be used to save
on space and increase operation efficiency of your power system, even in high temperature environments.
The maximum allowable ambient temperature for this class of wires is 90qC (194qF). The (Boardlex) wire
range available from Furukawa Electric Co., Ltd. satisfies these requirements.
Shielded-Twisted cables for internal wiring of electronic/electric equipment
Use this category of cables for the control circuits of the inverter so as to prevent the signal lines from
being affected by noise from external sources, including the power input/output lines of the inverter
themselves. Even if the signal lines are inside the power control cabinet, always use this category of cables
when the length of wiring is longer than normal. Cables satisfying these requirements are the Furukawa's
BEAMEX S shielded cables of the XEBV and XEWV ranges.

Table of Contents

Other manuals for Fuji Electric frenic mini series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric frenic mini series and is the answer not in the manual?

Fuji Electric frenic mini series Specifications

General IconGeneral
BrandFuji Electric
Modelfrenic mini series
CategoryInverter
LanguageEnglish

Related product manuals