Code Parameter Name / Range
07-30 Low Voltage Level Selection
(0) Disable
(1) Enable
07-30=1: The value of Low Voltage Detection Level (07-13) adjust to 250V for Inverter
400V class.
Code Parameter Name / Range
07-31 Low Voltage Run Frequency
0.0~599.00 Hz
07-31=1: When 03-00~03-07=62 (EPS Function),the frequency command will follow the value of 07-31
Please refer to 4-82 for more information to EPS function.
Code Parameter Name / Range
07-34 Start short-circuit braking time
0.00~100.00 s
07-35 Stop Short-circuit braking time
0.00~100.00 s
07-36 Short-circuit braking current limited
0.0~200.0%
PMSLV is available for short-circuit braking. Short-circuit braking is the way to switch IGBT to produce braking
torque. 07-06, 07-34 and 07-36 can adjust the braking process.
If 07-35=0, Inverter start from the minimum frequency.
The value of 07-36 is depend on differential motor rated current (i.e. motor rated current is 5A, 07-36=100% is
5A)
03-00~03-07=65 can control Short-circuit braking.
VDI100 • Instruction manual 201