Maximum output current capacity for terminal 10V is 20mA.
Multi-function analog output AO1 and AO2 are used for an analog output meter. Do not use these outputs
for feedback control.
Control board’s 24V and ±10V are to be used for internal control only, Do not use the internal power-supply
to power external devices.
3.10. Power Terminals
Terminal
230V Class: 0.75 ~ 18.5kW
400V Class: 0.75 ~ 30kW
230V Class: 22kW
400V Class: 37 ~ 160kW
R/L1
Input Power Supply
(For single phase use terminals R/L1 and S/L2)
S/L2
T/L3
B1/P
B1/P-
: DC power supply
-
B2 B1/P-B2: external braking resistor
-
·
- : DC power supply or connect braking
module
U/T1
Inverter outputV/T2
W/T3
E Ground terminal
230V Class: 0.75kW~1.5kW/ 400V Class: 0.75kW~2.2kW
Terminal screw size
T
M4 M4
230V Class: 2.2 ~ 22kW, 400V Class: 3.7 ~ 55kW
Terminal screw size
T
M4 M4
230V Class: 7.5kW, 400V Class: 7.5 ~ 11kW
Terminal screw size
T
M6 M6
230V Class: 11~18.5kW, 400V Class: 15 ~ 30kW
Terminal screw size
T
400V Class: 15kW (Size 3)
M6 M5
230V Class: 11~18.5kW,
400V Class: 15 ~ 22kW
M6 M6
400V Class: 30kW
M6 M8
Caution
26 VDI100 • Instruction manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran VDI100 Series and is the answer not in the manual?

gefran VDI100 Series Specifications

General IconGeneral
Brandgefran
ModelVDI100 Series
CategoryInverter
LanguageEnglish

Related product manuals