11.5. InputCurrentandFuseSpecications
230V class
Model Horse power kVA
100% of rated
output current
HD/ND
Single phase
Rated input
current
HD/ND
3 phases
Rated input
current
HD/ND
Three-phase
fuse rating
(A) (A) (A) (A)
1007
1 1.9 5/6 9.4/11.3 5.4/6.5 20
1015 2 3 8/9.6 14.7/17.9 8.5/10.3 30
2022 3 4.2 11/12 20.3/22.1 11.7/12.8 50
2037 5 6.7 17.5/22 - 18.7/22.3 50
2055 7.5 9.5 25/30 - 26.3/31.6 63
3075 10 12.6 33/42 - 34.5/41.7 100
4110 15 17.9 47/56 - 51.1/60.9 120
4150 20 22.9 60/69 - 65.2/75 150
4185 25 28.6 73/80 - 79.4/85.9 200
5220 30 32.4 85/110 - 92.4/119.6 250
400V class
Model
Horse
power
kVA
100% of rated output current
HD/ND
3 phases
Rated input current
HD/ND
Three-phase
fuse rating
(A) (A) (A)
1007
1 2.6 3.4/4.1 3.7/4.5 10
1015 2 3.2 4.2/5.4 5.3/5.9 16
1022 3 4.2 5.5/6.9 6.0/7.5 16
2037 5 7 9.2/12.1 9.6/11.6 25
2055 7.5 11.3 14.8/17.5 15.5/18.2 40
3075 10 13.7 18/23 18.7/24.0 50
3110 15 18.3 24/31 25.0/32.3 63
3150 / 4150 20 23.6 31/38 33.7/41.3 80
4185 25 29.7 39/44 42.4/47.8 100
4220 30 34.3 45/58 48.9/58.7 120
5300 40 45.7 60/73 65.2/78.3 150
5370 50 57.2 75/88 81.5/95.7 200
5450 60 69.3 91/103 98.9/112 250
5550 75 85.4 118/145 130/159 300
6750 100 114 150/168 159/181 400
6900 125 137 180/208 181/229 500
71100 150 165 216/250 229/275 600
71320 175 198 260/296 275/325 700
71600 215 225 295/328 325/361 700
Fuse type:
America: choose semiconductor fuse to comply with UL.
Europe: aR type.
Voltage Range: For 230V class inverter, use 300V class fuse.
For 400V class inverter, use 600V class fuse.
344 VDI100 • Instruction manual