4.8.3 Welding Outdoor Unit Pipes
NO TICE
1. Before welding refrigerant pipes, fully exhaust nitrogen from the refrigerant
pipes to avoid explosion and injuries.
2. Before welding pipes, take measures to protect nearby cables and components
from being burnt.
Step 1 Remove pipe plugs using a welding torch.
Step 2 Connect the gas and liquid pipes to the gas and liquid pipes of the indoor unit
respectively.
Step 3 Wrap the outdoor pipes with thermal insulation foam.
Figure 4-65 Welding outdoor unit pipes
----End
4.8.4 (Optional) Welding Pipes for the Low Temperature
Component
NO TICE
Before welding pipes, take measures to protect nearby cables and components
from being burnt.
To install a low temperature component horizontally, you are recommended to
place the low temperature component on one side of the outdoor unit. Figure
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 4 Installation
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 91

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals