EasyManuals Logo
Home>Huawei>Computer Hardware>NetCol5000-A050

Huawei NetCol5000-A050 User Manual

Huawei NetCol5000-A050
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #112 background imageLoading...
Page #112 background image
Step 4 Adjust the air exhausting speed until no bubble ows out of the needle valve.
Step 5 Tighten the cooling water side needle valve.
Step 6 Inject water to 0.8 MPa, and preserve the pressure for 24 hours. Then connect a
pressure gauge to a needle valve on the pipeline to measure the pressure. If the
reading remains unchanged, the pipe is not leaking. You can perform the following
operations.
----End
4.9 Installing Cables
4.9.1 Cable Connection Precautions
Check that the input power cable of the indoor unit has no reverse phase
sequence or open phase.
Keep cables away from the compressor, fan, and copper pipe (if unavoidable,
take protective measures), and connect cables securely.
The device must be grounded as required by local electrical regulations.
Before connecting cables, remove the power cable protective cover.
Cables must be routed in through the cable clips.
Power cables and ground cables are routed and bundled separately from
other types of cables.
4.9.2 Installing the Equipotential Ground Cable
Figure 4-80 shows the equipotential ground position.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 4 Installation
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 102

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals