No. Item Note
6 Major alarms
indicates the number of active major
alarms.
7 Minor alarms
indicates the number of active minor
alarms.
8 Warnings
indicates the number of active
warnings.
9 Status bar -
10 Alarm bar
You can tap in the alarm
bar to enter the active alarm screen that
displays all active alarms.
11 Login button/Logout
button
indicates that you have not
logged in to the system, and can tap the icon
to log in.
indicates that you
have logged in to the system as admin or
operator user, and can tap the icon to log out.
12 Teamwork control
button
indicates that there is no teamwork
control at present.
indicates that there is
teamwork control without alarms at present.
indicates that there is teamwork control
with alarms at present.
6.5 Setting Parameters
6.5.1 Setting T/H Sensors Parameters
Prerequisites
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip Step 2.
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor. Figure
6-10 is displayed.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 6 Power-On Commissioning
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 139

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals