– The wet lm humidier consumes less power, saving more than 95% of
energy compared with a traditional electrode humidier.
– Compared with a traditional electrode humidier, the wet lm humidier
has a longer service life and maintenance interval.
● Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
● Check valve
The check valve
eectively prevents gas or liquid backow.
● Dierential pressure switch
When the air lter is dirty or blocked, the dierential pressure switch triggers
an alarm, prompting for air
lter replacement.
● T/H sensor
The smart cooling product contains the negative temperature coecient
(NTC) temperature sensor and the return air T/H sensor.
2.2.2 Display Panel
Appearance
The 7-inch display panel with the true-color touchscreen provides user interfaces
for query, setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the precision smart cooling
product. Figure 2-6 shows the location of the indicator. Table 2-4 lists the
relationship of the alarm status, indicator, and buzzer. If critical alarms, major
alarms, and warning alarms are generated simultaneously, the indicator shows the
status of the alarm with the highest severity level, and the buzzer shows the
status of the alarm (not
conrmed after the alarm generation) with the highest
severity level.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 2 Product Description
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 19