Refrigera
nt Charge
Amount
Length
of the
One-
Way
Connecti
on Pipe
Between
the
Indoor
and
Outdoor
Units (L)
NetCol500-
A060
(NetCol500-
A120)
NetCol500-
A060 with
a Low
Temperatur
e
Component
NetCo
l500-
A080
NetCol500-
W055
Charge
amount
(kg) =
Standard
charge
amount +
Extra
charge
amount
10 m < L
≤ 60 m
9.2 + (L – 10)
x 0.19
20.2 + (L –
10) x 0.19
13.2 +
(L –
10) ×
0.19
10 + (L – 10)
× 0.21
Charge
amount
(kg) =
Standard
charge
amount +
Extra
charge
amount
60 m < L
≤ 100 m
9.2 + (L – 10)
x 0.25
20.2 + (L –
10) x 0.25
13.2 +
(L –
10) ×
0.25
10 + (L – 10)
× 0.28
NO TE
When the outdoor unit is NetCol500-A120, two indoor units can be connected.
6.1.2 Vacuumizing
Prerequisites
NO TICE
Before vacuumizing the cooling system, ensure that the refrigerant pipes have
passed the air tightness test and do not leak.
Before vacuumizing the cooling system, ensure that all connectors are secured.
System high pressure may occur if the cooling system is not vacuumized or is
not thoroughly vacuumized. Ensure that the cooling system is thoroughly
vacuumized before refrigerant is charged.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 6 Power-On Commissioning
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 122

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals