Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor Fan, and set
Air-side dierence pressure sensor type to 0–50 Pa.
Step 2 Set Indoor fan control type to Pressure di ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 6-6 Parameter description
Parameter Description Setting Rule
Indoor fan control type Species the control type
for the indoor fan.
Normally, retain R/S air
temp di rate ctrl. If
the dierential pressure
sensors are installed,
change to Pressure di
ctrl.
Indoor fan pressure
dierence setpoint
Species the dierential
pressure control
threshold.
The default value is 10
Pa. When there are
partial hot spots indoors,
you are advised to raise
the value to ensure that
the air volume of the
indoor fans is between
60%–70%.
Air-side dierence
pressure sensor type
Species the measuring
range for the air-side
dierential pressure
sensor.
There is no default value.
Set it to 0–50 Pa.
Min indoor fan speed Species the minimum
speed for the indoor fan.
The default value is 30%.
You are advised not to
change the value.
Max indoor fan speed Species the maximum
speed for the indoor fan.
The default value is
100%.
----End
6.5.3 (Optional) Setting Teamwork Control Parameters
Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
● Teamwork group No.: Group the smart cooling products in same aisle or
adjacent areas as one, that is, assign one teamwork group number for them.
At most four teamwork groups can be assigned (1–4).