10 Troubleshooting
CA UTION
Certain circuits in the smart cooling product have lethal voltages. Only
professional technicians are allowed to perform maintenance.
NO TICE
Exercise caution during live-line troubleshooting.
If jumpers are used for troubleshooting, remove them after troubleshooting.
Connected jumpers may aect control functions and damage equipment.
Table 10-1 describes how to troubleshoot the NetCol5000-A.
Table 10-1 Troubleshooting
Symptom
Possible Cause Solution
The unit
generates
abnormal
voice.
The compressor, fan, or pipes
are loose.
Check the xing structure and
ensure that all components are
securely installed.
The
compressor
does not
work.
The high-pressure switch
reacts.
Check the high-pressure switch
status.
Circuit breakers, fuses, or
cables are disconnected.
Check the main circuit breaker,
compressor circuit breakers,
fuses, and cables.
A compressor motor is
damaged.
Replace the motor.
A compressor does not need
to start.
Check the requirement status on
the display module.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 10 Troubleshooting
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 243

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals