Figure 11-35 Installing a liquid level detector
Step 7 Install the water pan cover, and close the front door.
Step 8 Power on the device and tap Startup on the home screen. Ensure that the smart
cooling product is running normally without any alarms.
----End
11.11 Replacing a Condensate Pump
Prerequisites
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: Phillips screwdriver,
at-head screwdriver, socket wrench
NO TICE
Before removing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump can be maintained only from the front door.
Procedure
Step 1 Tap Shutdown on the home screen of the controller, and turn o the active power
switch QF1 and standby power switch QF2. (For the model with a single power
supply, you do not need to turn
o QF2.)
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 11 Parts Replacement
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 279

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals