Figure 8-1 Removing a water pan lter
8.1.3 Quarterly Maintenance
Table 8-3 lists quarterly maintenance items for the indoor unit.
Table 8-3 Quarterly maintenance checklist
Compo
nent
Item (on the Basis of
Monthly Maintenance)
Troubleshooting
Monito
ring
Export smart cooling product
logs, alarms, temperature, and
humidity, as well as the
operating status and time of
the compressor, fan, electric
heater, electric
humidier, and
water pump from the
monitoring system. View the
historical alarms generated in
this quarter and select the
most common
ve ones. (If no
monitoring system is available,
skip this item.)
Rectify the fault or contact Huawei
technical support.
Wet
lm
humidif
ier
Start the device, choose Maint
> Diagnostic Mode > Enter
on the home screen, and start
the wet lm humidier.
If no water is supplied, check the
cable connection or replace the
water inlet solenoid valve.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 8 Maintenance
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 176

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals