6 Parameter Description
-
249
-
Function
Code
Name Setting Range Default Unit Property
FC-209 60
th
fault month and day 0 to 1231 0 MM.DD
FC-210
60
th
fault hour and
minute
0 to 23.59 0 HH.MM
If the 10 detailed fault records are full, the earliest detailed fault record will be moved
to the latest brief fault record. For example, if a new fault occurs, the fault code,
subcode and time information of the fault recorded in group E9 (fault information) will
be moved to FC-11 to FC-14.
the car is located when the fault occurs, and the two low digits indicate the fault code.
For example, the 1st fault record is 0835, indicating that when the latest brief fault
causes of the fault. Fault month and day and fault hour and minute record accurate
occurrence time of the fault.
Group Fd: Communication parameters
Function
Code
Name Setting Range Default Unit Property
Fd-00 Baud rate
0: 9600
1: 38400
1 -
☆
Fd-02 Local address
0: Broadcast
address
1 -
☆
Fd-03 Communication response delay 0 to 20 0 ms
☆
Fd-04 Communication timeout 0 to 60 0 s
☆
These RS232 serial port communication parameters are used for monitor software
communication in the host computer.
be consistent with the setting of the serial port parameters on the host computer.
each frame must be completed within the time set in Fd-04; otherwise, a communica-
tion fault occurs.
Function
Code
Name Setting Range Default Unit Property
Fd-05 Re-leveling stop delay 0.00 to 2.00 0.00 s
★
Fd-05 is used to set the re-leveling stop delay. The elevator decelerates to stop after
this delay after receiving a single leveling signal during re-leveling.