7 Troubleshooting
-
265
-
7.2 Restart after Fault
Stage Measures Remarks
When the fault
occurs
When F-2 is set to 2 with the keypad, it
displays the information about the last
10 faults, including fault code, subcode,
and time.
For details, refer to the parameter
description of groups E0 to E9
and FC-11 to FC-210.
Before the fault
is reset
Identify and eliminate any fault cause
according to a fault code displayed on
the operation panel.
Perform troubleshooting by
referring to "7.4 Fault Information
and Troubleshooting".
Fault reset
method
Automatic reset of faults
In case of some faults, if automatic
󶍾
troubleshooting, the controller
automatically resets faults.
Manual reset of faults
Some faults have to be manually reset
by pressing
STOP
RES
on the operation panel
or setting F-2 to 1 with the keypad.
Press the red Stop/Reset key on
the operation panel.
STOP
MF.K
RUN
STOP
RES
QUICK
PRG
ENTER
RES
Set F-2 to 1
󶍽
Some faults have to be reset by
󶍽
and turning it on again after
troubleshooting.
ON
OFF

Table of Contents

Other manuals for Inovance Monarch 220-NICE-L-C-4022F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance Monarch 220-NICE-L-C-4022F and is the answer not in the manual?

Inovance Monarch 220-NICE-L-C-4022F Specifications

General IconGeneral
BrandInovance
ModelMonarch 220-NICE-L-C-4022F
CategoryController
LanguageEnglish

Related product manuals