Configuration
7-107
48XX/49XXSHB0399
7.7.6 Monitoring of the serial interface
The controller detects an interruption because incoming telegrams are not
received.
( The monitoring is activated under C119 = -69- with C120 (default
setting = switched off).
( Reactions allowed are trip, warning, message and switched off.
( The time between cancelling the communication and activation of the
monitoring function is to be set under C126.
Code Name
Possible settings
Lenze Selection Info
C126* Time
delay(monitoring
serial interface)
3000 s 0.2 s {0.1 s} 10 s
10 s {1 s} 100 s
100 s {10 s} 3600 s
Note!
If a new parameter set is loaded, the time until the monitoring function is activated
starts again. The monitoring works independently of the RDY message.