7.8.5 Operating modes
The controller can be adapted to your application in different ways:
Terminals: The terminals are to control the controller.
Operating unit: There are five keys and the plain text display on the operating
unit for parameter setting and control of the controller.
LECOM1: LECOM1 is a protocol for control and parameter setting of the
unit via a PC or other hosts. The signals are processed to the
interface standards RS232C and RS485. The controller can be
connected to a superimposed system via X6.
LECOM2: For very difficult requirements, the controller can be parameter-
set and operated with LECOM2 via fieldbus connection
modules for standard bus systems (InterBus-S, PROFIBUS
etc.).
Code Name
Possible settings
Lenze Selection Info
C001¤ Operating
mode
0 Control Parameter setting
-0- Terminals Keypad
-1- Keypad Keypad
-2- Terminals LECOM1
-3- LECOM1 LECOM1
-4- Terminals LECOM2 (*)
-5- LECOM2 (*) LECOM2 (*)
-6- LECOM2 (*) Keypad
-7- LECOM2 (*) LECOM1
With C001 =
-2-, -3-, -4-, -5-, -7-, TRIP must be reset
(C043) via the interface or the terminal.
With LECOM2, TRIP reset is also possible
via the control word of the process data
channel.
(*) Fieldbus
Note!
With control via keypad, LECOM1 and LECOM2, the terminal functions controller
enable (X1/28), quick stop (X1/21 and X1/22) and the additional setpoint (X1/6)
remain the same in the configurations C005 = -1X-, -4X-, -5X-.