9300 Servo PLC
System blocks
2.10 DIGITAL_IO
2-37
L
ServoPLC EN 2.0
2.10.2 Outputs_DIGITAL
Digital outputs (module number 1)
This SB conditions the digital signals, and outputs them at terminals X5/A1 ... X5/A4.
X5
Outputs_DIGITAL
1
0
C0118/1...4
A3
A1
A4
A2
1
DIGOUT_bOut1_b
DIGOUT_bOut4_b
DIGOUT_bOut3_b
DIGOUT_bOut2_b
C0444/1...4
Fig. 2-21 Outputs_DIGITAL
VariableName
DataType SignalType Address DIS DIS format Note
DIGOUT_bOut1_b
%QX1.0.0 C0444/1
DIGOUT_bOut2_b
%QX1.0.1 C0444/2
DIGOUT_bOut3_b
Bool binary
%QX1.0.2 C0444/3
bin
DIGOUT_bOut4_b %QX1.0.3 C0444/4
Electrical data of the output terminals
Terminal Use Data
X5/A1
LOW level:
0 ... +4 V
X5/A2
HIGH level:
+13 ... +30 V
X5/A3
Freely assignable
u
pu
curren
: max. 50 m
per ou
pu
ex
ernal resis
ance ≥ 480 Ω a
24
X5/A4
Delay times:
100 µs ... 300 µs
X5/39 Ground (GND) of digital inputs and outputs
• The terminal polarity for the outputs A1 ... A4 can be configured under C0118.
Code LCD
Possible settings
Info
Lenze Selection
C0118 DIGOUT pol Terminal polarity
0 HIGH active
1LOWactive
1 0 X5/A1
2 0 X5/A2
3 0 X5/A3
4 0 X5/A4
efesotomasyon.com - Lenze