9 Visualization
Maschinenfabrik Reinhausen GmbH 2020118 6385142/08 ENETOS
®
ED
PTP hops
You can use this parameter to enter the number of network sections be-
tween master and slave. You can set up to 16 hops.
PTP version
You can use this parameter to select the PTP version.
▪ PTP version 1 (IEEE 1588-2002)
▪ PTP version 2 (IEEE 1588-2008)
PTP interface
You can use this parameter to select the interface that the device is to use
for PTP.
9.6 Configuring syslog
The device supports the transmission of log messages via the syslog proto-
col in accordance with the standards RFC5424 and RFC3164.
Reconnect delay time 10s
Emergency severity level Off
Critical severity level Off
Warning severity level Off
Notice severity level Off
Figure88: Syslog
1. Go to Settings > Parameters > System > Syslog.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
Activate syslog
You can use this parameter to activate transmission of syslog messages via
the device.