7 Commissioning
Maschinenfabrik Reinhausen GmbH 2020 996385142/08 EN ETOS
®
ED
2. Go to Settings > Commissioning wizard.
Figure78: Calling up the commissioning wizard
3. Press the Next button to launch the commissioning wizard.
4. Follow the on-screen instructions.
Once you have entered all of the parameters relevant to commissioning,
continue with the function test.
7.6.5 Checking measured values and status of digital inputs and
outputs
Upon commissioning the device, check whether the measured values and
status of digital inputs and outputs are plausible. To do so, use an additional
measuring device if necessary in order to check the individual measured val-
ues.
To display the status of the digital inputs and outputs, proceed as follows:
1. Go to Information > Hardware.
2. Select the individual assemblies one after another and check the individ-
ual measured values or the status of digital inputs and outputs.
3. If errors arise, check the measurement path and the wiring.
7.6.6 Checking the temperature measurement
To commission the device, check whether the measured temperatures are
plausible, the temperature sensors are correctly wired and are assigned to
the desired functions. To do so, proceed as follows:
1. Display the temperature curve [►Section 9.24.4, Page 253].
2. Use a suitable measuring instrument to measure the temperatures at the
measurement points and compare these values to the displayed tempera-
tures.
ð The temperatures must match, though small deviations are permitted
due to the measurement tolerances.