9 Visualization
Maschinenfabrik Reinhausen GmbH 2020242 6385142/08 ENETOS
®
ED
Behavior
You can use this parameter to set the behavior of the device when the event
message is issued. You can select the following options:
Setting Behavior
Off The limit value is not monitored.
Auto blocking Automatic regulation is blocked.
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking Automatic regulation is blocked.
You cannot perform tap-change operations in manual
mode.
Table79: Behavior when an event message is issued
9.22.9 Temperature monitoring
You can set different limit values for every measured/calculated temperature
. If the measured temperature is greater than limit value > or >>, the device
triggers an event message. If the measured temperature is less than limit
value < or <<, the device triggers an event message.
Parameters
Temperat...ing
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
Figure165: Temperature monitoring
1. Go to Settings > Parameters > Temperature monitoring.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
9.22.10 Switching interval monitoring
You can use this function to monitor the typical tap-change behavior of your
transformer.