6.4.5 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC stan-
dards. The following points must be noted in order to maintain the EMC
standards.
6.4.5.1 Wiring requirement of installation site
Note the following when selecting the installation site:
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
▪ Separate system parts must be joined by a potential equalization.
▪ The device and its wiring must be at least 10m away from circuit-break-
ers, load disconnectors and busbars.
6.4.5.2 Wiring requirement of operating site
Note the following when wiring the operating site:
▪ Route the connecting leads in grounded metal cable ducts.
▪ Do not route lines which cause interference (e.g. power lines) and lines
susceptible to interference (e.g. signal lines) in the same cable duct.
▪ Maintain a distance of more than 100 mm between lines which cause in-
terference and those which are susceptible to interference.
Figure66: Recommended wiring
1 Cable duct for lines causing inter-
ference
3 Cable duct for lines susceptible to
interference
2 Line causing interference (e.g.
power line)
4 Line susceptible to interference
(e.g. signal line)
▪ Short-circuit and ground reserve lines.
▪ Never connect the device with a multi-wire collective pipe.