6.4.5.5 Information about shielding the cables for analog signals
In order to correctly record the analog signals, you must place the cable
screening in the motor-drive unit on the grounding bar. The cable shielding
should only be removed just prior to connecting, to ensure that the section
with unshielded cables is kept as short as possible. The shielding must be
connected with shielding clips.
1
3
2
4
5
11
13
12
14
15
6
8
7
9
10
16
18
17
19
20
RDY
AIO 4
+
-
24V DC
11
12
13
14
15
16
17
18
20
19
1
2
3
4
5
6
7
8
9
10
Figure69: Examples of supporting shielding on grounding bar (on left: Direct connection to AIO
assembly, on right: Connection using line-up terminal)
6.4.6 Connecting cables to the system periphery
To obtain a better overview when connecting cables, only use as many
leads as necessary.
To connect cables to the system periphery, proceed as follows:
ü Use only the specified cables for wiring. Note the cable recommendation.
► Connect the lines to be wired to the device to the system periphery as
shown in the connection diagrams supplied.
6.4.7 Wiring the device
To obtain a better overview when connecting cables, only use as many
leads as necessary.
To wire the device, proceed as follows:
ü Note the connection diagram.
ü Only use the specified cables for wiring. Note the cable recommendation.
ü Wire the leads to the system periphery [►Section 6.4.6, Page 84].
1. Strip insulation from cables and wires.