9 Visualization
Maschinenfabrik Reinhausen GmbH 2020 2716385142/08 EN ETOS
®
ED
1. Go to Settings > Parameters > Active part > Tx statistics monitoring.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
Relative loss-of-life >/>>
With these parameters you can set the limit values for the relative loss-of-life
of the transformer.
Loss of life >/>>
You can use these parameters to set the limit values for the loss-of-life of the
transformer.
9.26.6.2 Displaying transformer statistics
You can display the calculated loss-of-life of the transformer.
Figure197: Transformer statistics
► Go to Information > Active part > Statistics.
9.26.7 Display current oil level/dehydrating breather values
The device displays an overview of the current oil level and the dehydrating
breather measured values. With dehydrating breathers with 2 cylinders, the
device displays the mean value or the value of respective active cylinder if
the dehydrating breather transmits information on the active cylinder to the
device.