9 Visualization
Maschinenfabrik Reinhausen GmbH 2020274 6385142/08 ENETOS
®
ED
Rogers analysis
Dörnenburg analysis
IEC 60599 analysis
9.27.1 Configuring DGA monitoring
For the DGA monitoring "DGA", you can set 3 limit values for the absolute
values and for the rates of increase. Depending on the device configuration,
you can monitor up to 11 DGA signals. You can also set the following pa-
rameters:
Sensor measuring accuracy
Reset diagnostic errors
Rates of increase evaluation interval
Relative moisture in oil default value
Use relative moisture in oil default value
Parameters
DGA monitoring
Measuring accuracy of the sensor 15.0%
Reset diagnostic error memory Off
Evaluation interval for rates of ... 7 days
C2H2 > 1.0ppm
C2H2 >> 10.0ppm
C2H2 >>> 35.0ppm
C2H4 > 50.0ppm
C2H4 >> 100.0ppm
C2H4 >>> 200.0ppm
C2H6 > 65.0ppm
C2H6 >> 100.0ppm
C2H6 >>> 150.0ppm
CH4 > 120.0ppm
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
Figure200: Configuring DGA monitoring
To set the DGA monitoring, proceed as follows:
1. Go to Settings > Parameters > DGA monitoring.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
Sensor measuring accuracy
You can use this parameter to enter the sensor measuring accuracy as a
percentage value. When doing so, refer to the sensor operating instructions.