14 Technical data
Maschinenfabrik Reinhausen GmbH 2020396 6385142/08 ENETOS
®
ED
CISPR 11 (EN 55011) Industrial, scientific and medical equipment - Radio-fre-
quency disturbance characteristics - Limits and methods
of measurement: Class A
CISPR 16-2-1 Procedure for measuring high-frequency emitted interfer-
ence (radio interference) and immunity - measurement of
conducted emitted interference: Class A
CISPR 16-2-3 Procedure for measuring high-frequency emitted interfer-
ence (radio interference) and immunity - measurement of
radiated emitted interference: Class A
CISPR 22 (EN 55022) Information technology equipment - Radio disturbance
characteristics - Limits and methods of measurement:
Class A
Table169: Emitted interference in accordance with IEC 61000-6-4
Environmental durability tests
IEC60529 With OT1205: Degree of protection IP52 for the front,
IP20 for the rear
Without OT1205: IP20
IEC 60068-2-1 Dry cold - 25 °C / 96 hours
IEC 60068-2-2 Dry heat 70 °C / 96 hours
IEC 60068-2-78 Constant moist heat
+ 40 °C / 93% / 4 days, no dew
ASTM D 4169-09 Standard Practice for Performance Testing of Shipping
Containers and Systems
DC 3, safety level II
IEC60255-21-1 Class
1
Oscillations (3 cycles, 0.5 g 1octave/min; 60 cycles, 1.0
g, 1octave/min)
IEC60255-21-2 Class
1
Shocks (11ms, 5 g, 15 g, 3axes)
IEC60255-21-3 Class
1
Earthquakes (1...35 Hz; 3.5 mm/1 g horizontal; 1.5
mm/0.5 g vertical; 1 octave/min, 10 min/axis)
Table170: Environmental durability tests