1-11
1
Single-Type
1-1. Unit Specifi cations
Ducted Type S-140PE1R5 / U-140PE1R5
INDOOR MODEL S–140PE1R5
PANEL MODEL –
OUTDOOR MODEL U–140PE1R5
Branch pipe MODEL –
PERFORMANCE TEST CONDITION ISO5151 / AS/NZS3823
POWER SUPPLY
ø, Hz 1ø 50 Hz 1ø 50 Hz
V 230 V 240 V 230 V 240 V Min Max
C
O
O
L
I
N
G
CAPACITY
kW 14.0 14.0 3.3 15.5
BTU/h 47800 47800 11300 52900
CURRENT A 2.62 2.70 17.8 17.2 – –
INPUT POWER
W 590 640 3.860 k 3.810 k – –
TOTAL W – 4.450 k 4.450 k 1000 6.200 k
ANNUAL CONSUMPTION TOTAL W *
4
– 2225 – – –
EER/AEER /STR RAT TOTAL (W/W) – –
3.15/3.12/–
3.15 3.30 2.50
Erp *
6
Pdsign kW ––––––
SEER (W/W) ––––––
Class ––––––
POWER FACTOR % – – 94 92 – –
NOISE INDOOR
(H/L)
dB–A 51/47
Power Level dB 73/69
NOISE OUTDOOR
(H/L)
dB–A 54/–
Power Level dB 71/–
H
E
A
T
I
N
G
CAPACITY
kW 16.0 16.0 4.1 18.0
BTU/h 54600 54600 14000 61400
CURRENT A 2.62 2.70 18.1 17.5 – –
INPUT POWER
W 590 640 3.960 k 3.910 k – –
TOTAL W – 4.550 k 4.550 k 1050 6.100 k
COP/ACOP /STR RAT TOTAL (W/W) – –
3.52/3.48/–
3.52 3.90 2.95
Erp *
6
Pdsign kW ––––––
Tbivalen ˚C ––––––
SCOP (W/W) ––––––
Annual consumption kWh ––––––
Class ––––––
POWER FACTOR % – – 95 93 – –
NOISE INDOOR
(H/L)
dB–A 51/47 – / /
Power Level dB 73/69 –
NOISE OUTDOOR
(H/L)
dB–A – 55/– / /
Power Level dB – 71/–
EXTRA LOW TEMP
TOTAL CAPACITY(kW)/INPUT POWER(W)/COP
–
MAX CURRENT(A)/MAX INPUT POWER(W) 2.9/0.66 k 3.0/0.71 k
30.0/6.650 k 30.0/6.850 k
/
STARTING CURRENT(A)/COMP OUTPUT(W) – –
19.5/3.0 K 19.0/3.0 K
/
NETWORK IMPEDANCE(ΩMAX.) – –
FM OUTPUT (W) 440 90 × 2 /
MOISTURE REMOVAL VOLUME L/h(Pt/h) 9.0 (18.9) –
Extarnal static pressure
Pa (mmAq)
100 (MIN10 – MAX150)
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 60 (2119)
HEAT m
3
/min (ft
3
/min) 60 (2119)
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 135 (4767)
HEAT m
3
/min (ft
3
/min) 120 (4238)
REFRIGERANT TYPE, AMOUNT g(oz) R410A 3.40 k (119.9) /
P
R
O
D
I
M
HEIGHT
:
H mm (inch) 430 (16–15/16) 1416 (55–3/4) /
WIDTH
:
W mm (inch)
1100(+100)
(
43–5/16(+3–15/16))
940 (37–1/32) /
DEPTH
:
D mm (inch) 700 (27–9/16) 340 (13–13/32) /
P
A
C
D
I
M
HEIGHT
:
H mm 515 1556 /
WIDTH
:
W mm 1315 1055 /
DEPTH
:
D mm 812 485 /
MASS
(NET) kg(lb) 53 98 /
(GROSS) kg(lb) 61 108 /
LAYERS LIMIT (actually) 6(7) 1(2)
Operation
Condition
Cool (DBT) 18˚C – 32˚C -15˚C – 46˚C
Heat (DBT) 16˚C – 30˚C -20˚C – 24˚C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)
ø
9.52(3/8) (Gas)
ø
15.88(5/8) (Liquid)
ø
9.52(3/8) (Gas)
ø
15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft) fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft) 5 – 75 (16.4 – 246.1) – –
I/D&O/D HEIGHT DIRRERENCE m (ft) 15 (OD located lower)/30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT g/m (oz/ft) 50 (537.6)
PIPE LENGTH FOR ADDITIONAL GAS m (ft) 30 (98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet–bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V (400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
Sec1.indb11Sec1.indb11 2012/03/0717:29:562012/03/0717:29:56