SELECTING THE LOCATION FOR THE INDOOR UNIT
Required Minimum Space for Installation and Service.
Provide a check port on the piping side ceiling for repair and maintenance.
● Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air intet and outlet, and must allow spreading of air throughout the
room.
* If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.
INSTALLATION OF INDOOR UNIT
POSITION OF SUPENSION BOLT
(unit: mm)
ABCD
S-60PE1RS 1060 1100 540 700
S-71PE1R5
1060 1100 540 700
S-100PE1R5
S-125PE1R5
S-140PE1R5
Uintmm Ha
S-60PE1R5 290
S-71PE1R5 360
S-100PE1R5 360
S-125PE1R5 430
S-140PE1R5 430
* The Ha is necessary for the access to the
top of the unit for repair.
Uintmm Ha
S-60PE1R5 290
S-71PE1R5 360
S-100PE1R5 360
S-125PE1R5 430
S-140PE1R5 430
* The Ha is necessary for the access to the
top of the unit for repair.
● Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
● Install the unit leaning to a drainage hole side as a
figure for water drainage.
● Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
● Install the unit leaning to a drainage hole side as a
figure for water drainage.
TYPE A B C D
S-60PE1RS 130 33.1 290 118
S-71PE1R5
S-100PE1R5
195 35.7 360 50
S-125PE1R5
S-140PE1R5
260 38.2 430 1215
TYPE A B C D
S-60PE1RS 130 33.1 290 118
S-71PE1R5
S-100PE1R5
195 35.7 360 50
S-125PE1R5
S-140PE1R5
260 38.2 430 1215