1-3
1
Single-Type
1-1. Unit Specifi cations
4-Way Cassette Type S-71PU1R5 / U-71PE1R5
INDOOR MODEL
S–71PU1R5
PANEL MODEL
CZ–KPU2
OUTDOOR MODEL
U–71PE1R5
Branch pipe MODEL
–
PERFORMANCE TEST CONDITION
ISO5151 / AS/NZS3823
POWER SUPPLY
ø, Hz
1ø 50 Hz 1ø 50 Hz
V
230 V 240 V 230 V 240 V Min Max
C
O
O
L
I
N
G
CAPACITY
kW
7.1 7.1 2.5 8.0
BTU/h
24200 24200 8500 27300
CURRENT A
0.33 0.32 8.10 7.90 – –
INPUT POWER
W
40 40 1.760 k 1.760 k – –
TOTAL W
– 1.800 k 1.800 k 450 2.650 k
ANNUAL CONSUMPTION TOTAL W *
4
– 900 – – –
EER/AEER /STR RAT TOTAL (W/W)
–––
3.94/3.85/2.5
3.94 5.56 3.02
POWER FACTOR %
– – – 94 93
NOISE INDOOR
(H/M/L)
dB–A
37/31/28
Power Level dB
54/48/45
NOISE OUTDOOR
(H/L)
dB–A
48/–
Power Level dB
65/–
H
E
A
T
I
N
G
CAPACITY
kW
8.0 8.0 2.0 9.0
BTU/h
27300 27300 6800 30700
CURRENT A
0.32 0.31 9.00 8.70 – –
INPUT POWER
W
40 40 1.960 k 1.960 k – –
TOTAL W
– 2.000 k 2.000 k 400 2.900 k
COP/ACOP /STR RAT TOTAL (W/W)
–––
4.00/3.91/3.0
4.00 5.00 3.10
POWER FACTOR %
– – 95 94 – –
NOISE INDOOR
(H/M/L)
dB–A
37/31/28 – / /
Power Level dB
54/48/45 –
NOISE OUTDOOR
(H/L)
dB–A
– 50/– / /
Power Level dB
– 67/–
EXTRA LOW TEMP
TOTAL CAPACITY(kW)/INPUT POWER(W)/COP
–
MAX CURRENT(A)/MAX INPUT POWER(W)
– 0.33/40 0.32/40
18.0/3.930 k 18.0/4.060 k
/
STARTING CURRENT(A)/COMP OUTPUT(W)
–––
9.00/2.0 K
8.70/2.0 K
/
NETWORK IMPEDANCE(ΩMAX.)
––
FM OUTPUT (W)
60 90 /
MOISTURE REMOVAL VOLUME L/h(Pt/h)
4.2 (8.8) –
Extarnal static pressure
Pa (mmAq)
–
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min)
22 (777)
HEAT m
3
/min (ft
3
/min)
22 (777)
O/D AIR FLOW
COOL m
3
/min (ft
3
/min)
60 (2119)
HEAT m
3
/min (ft
3
/min)
60 (2119)
REFRIGERANT TYPE, AMOUNT g(oz)
R410A 2.35 k (82.9) /
P
R
O
D
I
M
HEIGHT
:
H mm (inch)
256 (10–3/32) 996 (39-7/32) /
WIDTH
:
W mm (inch)
840 (33–3/32) 940 (37–1/32) /
DEPTH
:
D mm (inch)
840 (33–3/32) 340 (13–13/32) /
P
A
C
D
I
M
HEIGHT
:
H mm
298 1136 /
WIDTH
:
W mm
929 1055 /
DEPTH
:
D mm
929 485 /
MASS
(NET) kg(lb)
24(53) 69(153) /
(GROSS) kg(lb)
29(64) 77(170) /
LAYERS LIMIT (actually)
11(12) 2(3)
Operation
Condition
Cool (DBT)
18˚C – 32˚C -15˚C – 46˚C
Heat (DBT)
16˚C – 30˚C -20˚C – 24˚C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)
ø
9.52(3/8) (Gas)
ø
15.88(5/8) (Liquid)
ø
9.52(3/8) (Gas)
ø
15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 – 50 (16.4 – 164.0) – –
I/D&O/D HEIGHT DIRRERENCE m (ft)
15 (OD located lower)/30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT g/m (oz/ft)
50 (537.6)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30 (98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
Sec1.indb3Sec1.indb3 2012/03/0717:29:542012/03/0717:29:54