Building Technologies 10 Parameterization 29.07.2010
10.2 Differences between SED2 firmware versions 1.20 and 1.30
Parameter Description Version 1.20 Version 1.30
P1200
Flying start Def: 0 Def: 3
P1202
Motor current: Flying start Def: 100% Def: 50%
P1203
Search rate: Flying start Def: 100% Def: 50%
P1210
Automatic restart
Max: 5
Number of possible settings: 5
Max: 6
Number of possible settings: 6
Setting 6: Restart after mains
brownout / blackout
or failure,
P1211 disabled
P1800
Pulse frequency
Min: 2 Min: 4
P2192
Time delay for belt failure
Max: 65
Def: 10
Max: 600
Def: 10
10.3 Differences between SED2 firmware versions 1.30 and 1.4x
Parameter Description Version 1.30 Version 1.4x
P1074 [2]
Disables additional setpoint
Not available
New; level 3
(for details, see ”Parameter list”)
P1210
Automatic restart Max: 6 Max: 7
Setting 7:
The VSD acknowledges error F0003 and
others during startup after a mains failure
or mains undervoltage and initiates motor
restart. The ON command must be
delivered via a digital input (DIN). The
motor is immediately restarted. P1211
defines the number of restart attempts.
When the defined number of restart
attempts are reached, error relay P0731
switches to 52.3, if parameterized. If no
error is recorded within a period of 2
hours, the error storage will be reset
(deleted).
P1271 [2]
ESM control word Not available New; level 3
(for details, see ”Parameter list”)